EN  

AMC72-DV DC Voltage Meter

AMC72-DV


•DC voltage metering
•Measure voltage in DC system
•DI/DO, Relay alarm output


Description

General


AMC series programmable intelligent meters, adopting DC sampling technology, can directly or indirectly measure electric voltage and current of single phase or three phase grid. It can be used for local display, and connecting industrial control device to form measuring control system.


Parameters




Accuracy

Current:Class 0.5

Power Supply

AC 220V

Current:Power consumption

< 0.5VA

Power supply

power consumption≤5VA

Installation

Embedded installing

Starting current

0.3%






Faceplate(L×W)

75*75mm

Cutout(L×W)

67*67mm

Housing(L×W×H)

66*66*98mm

Switch relay

DC 30V/3A AC 220V/3A


Technical Datasheet



Technical Parameter
Value






Input

Rated Value

AC voltage:Single phaseAC 100V,400V

Three phaseAC 100V,400V,660V(UL-L,Only 72/ 96)

AC current:AC1A,5A;

DC voltage:1000V,300V,75mV,10V;

DC current: 0-20mA,4-20mA,5A;

Overload

Voltage: 1.2 times rated value(continuous); 2 times rated value /1 second

Current:1.2 times rated value(continuous); 10 times rated value /1 second

Frequency

45Hz~65Hz

Power Consumption

Power consumption of each voltage,current input circuit is less than 0.5VA

AccuracyClass 0.5






Function

Display

LED or LCD

Communication

RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity)

Baud Rate 2400/4800/9600/19200 bps etc.

Alarm

1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC, Used for high,low,unbalance alarm etc.

Analog

DC4~20mA,( load <500Ω)

(note:Shielded wire is specially selected for the above signal input and output)

Switching

Input:4 channel or 2 channel dry contact Input,built in power supply

Output:2 channel switching output,NO relay contact,capacity:3A/30VDC,3A/250VAC

Auxiliary Supply

AC/DC 85-265V

Power Consumption

<5VA

Insulation resistance

≥ 100MΩ

Power frequency withstand voltage

Between power supply set of terminals and signal input,output set of terminals 2kV/1min (RMS)

Between the shell and all set of terminals(except the set of terminals reference voltage less than 40V) AC 4kV


Environment

Temperature

Operation: -10℃~+55℃Storage: -25°C ~+70°C

Humidity

≤95%RH,no condensation,without corrosive gas

Altitude

≤ 2500m


Dimensions





Wiring



Network




Installation




FAQ




Q: No display on power?


A: Check whether the supply voltage is within the operating voltage range.



Q: Incorrect reading of voltage,current,electricty,etc?


A: Checking that the voltage/current ratio setting are correct;

     Checking whether the wiring mode setting is consistent with the actual situation;

     Checking whether the voltage transformer and current transformer are in good condition.



Q: Abnormal communication?


A: Check whether the adress,baud rate,check bits in the communication;

     Setting are consistent with the host computer;

     Check whether the RS485 converter is normal;

     Check the connection is corrent if the resistor above 120 ohm is connected in parallel at the communication end.


Package




MINIMUM PACKAGE







MINIMUM PAKAGE


Package dimensions(1 PC)

230*145*120mm

Pakage Weight(1 PC)

0.58Kg


WHOLE BOX PAKAGE


Package dimensions(48PCS)

615*480*120mm

Pakage Weight(48 PCS)

13.5kG


PRODUCT HS CODE


9028301300

ATTENTION !

The above packing and weight data are only refer to model AMC72-DV.

For other models or optional functions, please contact the salesman for details, thank you for your cooperation!




Inquiry Now

Would you like to get information about Acrel? We appreciate your interest and would be happy to advise you.Simply give us some information so we can get in touch with you

GET YOUR FREE QUOTE

We will contact you within 24 hours.

X